[{"data":1,"prerenderedAt":27},["ShallowReactive",2],{"content-cable-voltage-drop-en":3},{"about":4,"steps":7,"faq":11},[5,6],"The longer and thinner a cable, the more voltage is lost on the way to the load. The calculator gives the voltage drop as ΔU = 2 · l · I · cos φ \u002F (κ · A) for DC and single-phase AC (outgoing and return conductor) or √3 · l · I · cos φ \u002F (κ · A) for a balanced three-phase load, with κ = 56 m\u002F(Ω·mm²) for copper and 35 for aluminium.","The other way round it finds the smallest standard cross-section from 0.5 to 240 mm² for a maximum drop. Instead of the current you can enter the load’s power; it also shows the voltage at the load and the power lost in the cable.",[8,9,10],"Choose whether you want the drop for a cross-section or the cross-section for a maximum drop, and the system.","Enter the voltage, the current or power and the one-way cable length; for AC optionally the cos φ.","Pick the conductor material and the cross-section or the allowed drop in percent and read the result.",[12,15,18,21,24],{"q":13,"a":14},"How much voltage drop is allowed?","For German house installations DIN 18015-1 recommends at most 3 % between meter and load; IEC 60364-5-52 (DIN VDE 0100-520) suggests 4 %. 12 V systems in vehicles or solar setups often aim for 1–3 % because even a few tenths of a volt matter.",{"q":16,"a":17},"Which length do I enter?","The one-way distance from the supply to the load. The formula adds the return conductor itself with the factor 2 for DC and single-phase AC, and √3 for three-phase.",{"q":19,"a":20},"Is the calculated cross-section also enough thermally?","Not necessarily. The calculator only checks the voltage drop. How much current a cable can carry continuously depends on how it is laid, grouping and ambient temperature (IEC 60364-5-52, DIN VDE 0298-4) – for short cables that is often the limit. For traces on circuit boards use the [[pcb-trace-width]] calculator.",{"q":22,"a":23},"Why is the drop smaller with three-phase?","With a balanced load no current flows in the neutral, and the power is shared by three line conductors. Relative to the higher line-to-line voltage of 400 V the percentage drop is therefore much smaller than for the same power at 230 V.",{"q":25,"a":26},"How do I convert between current and power?","For DC I = P \u002F U, for single-phase AC I = P \u002F (U · cos φ) and for three-phase I = P \u002F (√3 · U · cos φ). DC relationships are also covered by [[ohms-law]].",1794509133748]