Heat Load & Heat Pump Calculator

Rough heat load of a home from living area or previous gas/oil consumption – with heat pump size, power consumption and running costs.

Runs locally in your browser
Heat pump output
9.9 kW
Building heat load · 65 W/m²9.10 kW
Hot water · 1,800 kWh per year0.75 kW
Heating demand18,200 kWh
Heat pump electricity5,714 kWh
Electricity cost per year€1,600

Rough estimate for planning and plausibility checks. A heat pump is sized with a room-by-room heat load calculation per DIN EN 12831 – ask your installer for one.

About this tool

The heat load is the power a house needs on the coldest day to stay warm. It determines how big a heat pump has to be: too small, and the backup heater kicks in often; too big, and the unit cycles and runs inefficiently. The calculator estimates the heat load either from living area and building standard or – often more accurately – from the previous gas or oil consumption.

It adds hot water and any blocking times of the grid operator during which the heat pump may not run. With the seasonal performance factor it works out how much electricity the heat pump needs per year and what that costs. Everything runs in your browser and does not replace a room-by-room heat load calculation.

How it works

  1. Choose the method: by living area with building standard, or by the consumption on your last heating bill.
  2. Enter persons for hot water, any blocking time, the expected seasonal performance factor and your electricity tariff.
  3. Read the recommended heat pump output, the heat load, the electricity consumption and the cost.

Frequently asked questions

How do I calculate the heat load from gas consumption?

Consumption times the efficiency of the old boiler gives the heat actually needed. Divided by the full load hours – in Germany usually around 2000 h – this gives the heat load. 20,000 kWh of gas at 90 % efficiency is about 9 kW.

What do the W/m² values mean?

They are guide values for the specific heat load: about 120 W/m² in an unrenovated old building, 65 W/m² after a good renovation and 30 W/m² in an efficiency house. Real values depend on location, geometry and ventilation.

Why does the blocking time increase the output?

If the grid operator may block the heat pump for up to 6 hours a day, it has to deliver the heat in the remaining hours. The calculator therefore scales the output by 24 / (24 − blocking hours).

Which seasonal performance factor is realistic?

Air-to-water heat pumps often reach 3.5 to 4.5 in well-insulated houses with underfloor heating, rather 2.8 to 3.5 in old buildings with radiators. Ground source heat pumps are higher.

Is a heat pump cheaper than gas?

That depends on prices and the performance factor. Compare the annual costs with the Heating Cost Comparison. Whether walls stay dry after a renovation is shown by the Dew Point & Mold Risk Calculator calculator.