Cable Voltage Drop Calculator

Voltage drop and power loss of a cable – or the smallest cross-section for a maximum drop – for DC, single-phase and three-phase, copper or aluminium.

Runs locally in your browser
V
A
m
Voltage drop
7.62 V · 3.31 %
Voltage at the load222 V
Load current16 A
Power loss in the cable122 W

Only the voltage drop is calculated. The current-carrying capacity of a cable also depends on how it is laid and must be checked separately (e.g. DIN VDE 0298-4).

About this tool

The longer and thinner a cable, the more voltage is lost on the way to the load. The calculator gives the voltage drop as ΔU = 2 · l · I · cos φ / (κ · A) for DC and single-phase AC (outgoing and return conductor) or √3 · l · I · cos φ / (κ · A) for a balanced three-phase load, with κ = 56 m/(Ω·mm²) for copper and 35 for aluminium.

The other way round it finds the smallest standard cross-section from 0.5 to 240 mm² for a maximum drop. Instead of the current you can enter the load’s power; it also shows the voltage at the load and the power lost in the cable.

How it works

  1. Choose whether you want the drop for a cross-section or the cross-section for a maximum drop, and the system.
  2. Enter the voltage, the current or power and the one-way cable length; for AC optionally the cos φ.
  3. Pick the conductor material and the cross-section or the allowed drop in percent and read the result.

Frequently asked questions

How much voltage drop is allowed?

For German house installations DIN 18015-1 recommends at most 3 % between meter and load; IEC 60364-5-52 (DIN VDE 0100-520) suggests 4 %. 12 V systems in vehicles or solar setups often aim for 1–3 % because even a few tenths of a volt matter.

Which length do I enter?

The one-way distance from the supply to the load. The formula adds the return conductor itself with the factor 2 for DC and single-phase AC, and √3 for three-phase.

Is the calculated cross-section also enough thermally?

Not necessarily. The calculator only checks the voltage drop. How much current a cable can carry continuously depends on how it is laid, grouping and ambient temperature (IEC 60364-5-52, DIN VDE 0298-4) – for short cables that is often the limit. For traces on circuit boards use the PCB Trace Width Calculator calculator.

Why is the drop smaller with three-phase?

With a balanced load no current flows in the neutral, and the power is shared by three line conductors. Relative to the higher line-to-line voltage of 400 V the percentage drop is therefore much smaller than for the same power at 230 V.

How do I convert between current and power?

For DC I = P / U, for single-phase AC I = P / (U · cos φ) and for three-phase I = P / (√3 · U · cos φ). DC relationships are also covered by Ohm’s Law Calculator.